BC1000B2019

Email
The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.
bc1000nl01colres.jpg
Usually ships in 15 to 20 days
 
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals
CE approved according EN298 (for intermittent operation)
GOST
AGA
Protection class IP00
Ambient temperature -20 ... 60 oC
Maximum humidity 90 %rh
Note
The BC1000A1/B1 models will operate also with the "Satronic" IRD820/1020 range of infrared sensors. Note that this combination is NOT CE approved for use on installations that fall under the GAD (Gas Appliances Directive).
Additional description
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
applcertmarkcege23 applcertmarkghostge23
Manufacturer: Honeywell
Outputs 1xSPDT
Operation Flame switch
Flame failure response time <1s
Flame detector UV
Supply voltage 220..240 Vac
Comment C7027, C7035, C7044
Specification Sheet
Cookies make it easier for us to provide you with our services. With the usage of our services you permit us to use cookies.