Flame relays BC1000

The BC1000A/B series is a flame switch for intermittent operation to indicate presence or absence of a flame and to be applied in commercial or industrial burner installations.

 
The BC1000A is specially designed to be used as manual start/stop burnercontroller. For all type of burners with unlimited capacity.
Approvals
CE approved according EN298 (for intermittent operation)
GOST
AGA
Protection class IP00
Ambient temperature -20 ... 60 oC
Maximum humidity 90 %rh
Note
The BC1000A1/B1 models will operate also with the "Satronic" IRD820/1020 range of infrared sensors. Note that this combination is NOT CE approved for use on installations that fall under the GAD (Gas Appliances Directive).
Additional description
BC1000A/B provides a Safe Start function which checks if a flame signal is present when applying power to the device.
BC1000A1/B1 models are for use with rectification type flame sensors, such as flame rods and C7012A/G UV sensors.
BC1000A2/B2 models are for use with Honeywell UV sensor models C7027, C7035 and C7044.
applcertmarkcege23 applcertmarkghostge23
Product Name Outputs Operation Flame failure response time Flame detector Supply voltage Comment Price (Excl. Tax)
BC1000A0220F 1xSPST Manual stop/start 2s Rectification 220..240 Vac Flame rod (or C7012A/G)
BC1000A0220U 1xSPST Manual stop/start 2s UV 220..240 Vac C7027, C7035, C7044
BC1000B1018 1xSPDT Flame switch <1s Rectification 220..240 Vac Flame rod (or C7012A/G)
BC1000B2019 1xSPDT Flame switch <1s UV 220..240 Vac C7027, C7035, C7044
BC1000A0110F 1xSPST Manual stop/start 2s Rectification 110..120 Vac Flame rod (or C7012A/G)
BC1000A0110U 1xSPST Manual stop/start 2s UV 110..120 Vac C7027, C7035, C7044
BC1000B1000 1xSPDT Flame switch <1s Rectification 110..120 Vac Flame rod (or C7012A/G)
BC1000B2001 1xSPDT Flame switch <1s UV 110..120 Vac C7027, C7035, C7044