UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals
CE approved according to EN298 only in combination with matching Honeywell flame amplifiers and burner controls.
C7061-series models are approved for use in continuous operation, by using dynamic self-check.
C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Ambient temperature -40 ... 80 oC
Additional description
Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply.
The "DIN" models have an additional grounding wire (green/yellow)
applcertmarkcege23 applcertmarkfmnl05 applcertmarkulge51 applcertmarkcsauscnl05
Product Name Operation ATEX Mechanical connection Cable length (m) Protection class Comment Note Price (Excl. Tax)
C7061A1004/U continuous with mechanical shutter No 3/4 2,4 IP66 Single shutter coil voltage: 120V only
C7061A1020/U continuous with mechanical shutter No 3/4 IP66 Dual shutter coil voltage: 120/230V
C7061A1079/U continuous with mechanical shutter No 3/4 IP66 With focussing lens Dual shutter coil voltage: 120/230V
C7061F1003 continuous with mechanical shutter Ex: CENELEC II G Ex d IIC T6; zone 1&2 1 IP67 Incl. cable gland Dual shutter coil voltage: 120/230V
Product Name Description Price (Excl. Tax)
114465/U Gasket, silicone rubber. For installing viewing window or lens(3pcs required)
118367A/U Swivel mount for adjustable positioning of the UV sensor
124198/U Mounting flange with 1" NPT internal thread for mounting on 1" sight pipe (to replace standard 3/4" NPT flange), for C7012A/E/G only
124204/U Quartz focussing lens
Product Name Description Price (Excl. Tax)
129464N/U Ultraviolet sensing tube (-40o to 121oC) for C7035 sensor
190971B/U Coil and shutter assembly for C7012E/F models only