UV flame sensors C7061A/F

Solid-state electronic UV flame sensor to detect ultraviolet radiation emitted by the combustion of most carbon-containing fuels such as natural gas, LP gases, and oil.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications.
Approvals
• CE approved according to EN298 only in combination with matching Honeywell flame amplifiers and burner controls.
• C7061-series models are approved for use in continuous operation, by using dynamic self-check.
• C7061F1 models are ATEX approved for use in explosion hazardous locations; II G Ex d IIC T6, zone 1&2.
• C7061F2 models are UL listed for use in explosion hazardous locations; Class 1, groups C and D; and Class 2, groups E, F, and G.
Ambient temperature -40 ... 80 oC
Additional description
• Two flame detectors can be wired in parallel to reduce nuisance shutdowns in difficult flame sighting applications.
• Quick and easy installation on standard 3/4" NPT sight pipe (Ex-proof models: 1" NPT).
• Uses the same UV sensing ("Power") tube as used with C7027/35/44 series "MiniPeeper": no external power supply.
• The "DIN" models have an additional grounding wire (green/yellow)
applcertmarkcege23 applcertmarkfmnl05 applcertmarkulge51 applcertmarkcsauscnl05
Product Name Operation ATEX Mechanical connection Cable length (m) Protection class Comment Note Price (Excl. Tax)
C7061A1004/U continuous with mechanical shutter No 3/4 2,4 IP66 Single shutter coil voltage: 120V only
C7061A1020/U continuous with mechanical shutter No 3/4 IP66 Dual shutter coil voltage: 120/230V
C7061A1079/U continuous with mechanical shutter No 3/4 IP66 With focussing lens Dual shutter coil voltage: 120/230V
C7061F1003 continuous with mechanical shutter Ex: CENELEC II G Ex d IIC T6; zone 1&2 1 IP67 Incl. cable gland Dual shutter coil voltage: 120/230V
Product Name Description Price (Excl. Tax)
114465/U Gasket, silicone rubber. For installing viewing window or lens(3pcs required)
118367A/U Swivel mount for adjustable positioning of the UV sensor
124198/U Mounting flange with 1" NPT internal thread for mounting on 1" sight pipe (to replace standard 3/4" NPT flange), for C7012A/E/G only
124204/U Quartz focussing lens
Product Name Description Price (Excl. Tax)
129464N/U Ultraviolet sensing tube (-40o to 121oC) for C7035 sensor
190971B/U Coil and shutter assembly for C7012E/F models only