Burner Controls EC/RM7800 series
The EC/RM7800 series are microprocessor-based industrial burner controls for automatically fired gas, oil or combination fuel single burner applications.
For all type of burners with unlimited capacity.
| Approvals |
|
||||||||
| Ambient temperature | -40 ... 60 oC | ||||||||
| Maximum humidity | 85 %rh | ||||||||
| Note | About Flame Failure Response Times (FFRT):
|
||||||||
| Flame detector | Depends on plug-in amplifier |
| Additional description |
|
![]()
| Product Name | Power | Control model | Outputs | Operation | Pilot | Prepurge timer | Pilot ignition time | Main ignition time | Post purge time | Number of ignition attempts | Flame failure response time | Comment | Price (Excl. Tax) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| RM7838C1004/U | 120Vac |
Full |
HF/LF/Modulate |
Continuous |
Interrupted |
• |
4/10s |
— |
— |
— |
0,8/3,0s |
— |
|
| EC7890A1011/U | 230Vac |
Primary |
HF/LF/Modulate |
Continuous |
Intermittent |
— |
4/10s |
— |
— |
— |
0,8/3,0s |
No shutter check |
|
| RM7840E1016/U | 120Vac |
Full |
HF/LF/Modulate |
Cont. |
Interrupted |
• |
4/10s |
— |
15s |
— |
0,8/3,0s |
|
|
| EC7890B1010/U | 230Vac |
Primary |
HF/LF/Modulate |
Continuous |
Intermittent |
— |
4/10s |
— |
— |
— |
0,8/3,0s |
— |
|
| RM7840G1014/U | 120Vac |
Atmosferic |
LF/Modulate |
Continuous |
Interrupted |
• |
4/10s |
— |
15s |
— |
0,8/3,0s |
— |
|
| RM7824A1006/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
— |
— |
4/10s |
— |
— |
— |
0,8/3,0s |
C7024E/F UV detector only |
|
| RM7840L1018/U | 120Vac |
Full |
HF/LF/Modulate |
Cont. |
Interrupted |
• |
4/10s |
— |
15s |
— |
0,8/3,0s |
|
|
| RM7850A1001/U | 120Vac |
Full |
HF/LF/Modulate |
Continuous |
Selectable |
• |
3/5s |
3/5s |
2s |
1 |
1,0/2,0s |
— |
|
| RM7840L1026/U | 120Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
4/10s |
— |
15s |
— |
0,8/3,0s |
|
|
| RM7850A1019/U | 120Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
3/5s |
3/5s |
15s |
1 |
1,0/2,0s |
|
|
| RM7840L1075/U | 120Vac |
Full |
HF/LF/Modulate |
Cont. |
Interrupted |
• |
4/10s |
— |
15s |
— |
0,8/3,0s |
Uses S7800A1142/U display for programming, Valve proofing system: Integrated |
|
| RM7850A1027/U | 120Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
3/5s |
3/5s |
30s |
1 |
1,0/2,0s |
|
|
| RM7840M1017/U | 120Vac |
Atmosferic |
on/off |
Cont. |
Interrupted |
— |
4/10s |
— |
15s |
— |
0,8/3,0s |
|
|
| EC7820A1026/U | 230Vac |
Atmosferic |
LF/Modulate |
Continuous |
Selectable |
• |
5/10s |
5/10s |
— |
1 |
1,0/2,0s |
— |
|
| RM7885A1015/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
— |
— |
4/10s |
— |
— |
— |
0,8/3,0s |
— |
|
| EC7820A1034/U | 230Vac |
Atmosferic |
LF/Modulate |
Continuous |
Selectable |
• |
5/10s |
5/10s |
— |
3 |
1,0/2,0s |
— |
|
| RM7890A1015/U | 120Vac |
Primary |
— |
Intermit. |
Intermittent |
— |
4/10s |
— |
— |
— |
0,8/3,0s |
No shutter check |
|
| EC7850A1064/U | 230Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
3/5s |
3/5s |
15s |
1 |
1,0/2,0s |
|
|
| RM7890B1014/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
Intermittent |
— |
4/10s |
— |
— |
— |
0,8/3,0s |
— |
|
| EC7850A1072/U | 230Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
3/5s |
3/5s |
2s |
1 |
1,0/2,0s |
|
|
| RM7890B1030/U | 120Vac |
Primary |
— |
Cont. |
Intermittent |
— |
— |
— |
— |
— |
0,8/3,0s |
Fixed 4s safety time. |
|
| EC7850A1080/U | 230Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
3/5s |
3/5s |
30s |
1 |
1,0/2,0s |
|
|
| RM7895A1014/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
Intermittent |
• |
4/10s |
— |
— |
— |
0,8/3,0s |
No air flow switch check, no delayed main valve |
|
| EC7850A1122/U | 230Vac |
Full |
HF/LF/Modulate |
Cont. |
Selectable |
• |
3/5s |
3/5s |
15s |
1 |
1,0/2,0s |
|
|
| RM7895B1013/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
Intermittent |
• |
4/10s |
— |
— |
— |
0,8/3,0s |
With air flow switch check, but no delayed main valve |
|
| EC7890B1028/U | 230Vac |
Full |
HF/LF/Modulate |
Continuous |
— |
— |
5/10s |
— |
— |
selectable |
1,0/2,0s |
— |
|
| RM7895C1020/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
Intermittent |
• |
4/10s |
10s |
— |
— |
0,8/3,0s |
No air flow switch check, but with delayed main valve |
|
| RM7823A1016/U | 120Vac |
Full |
2xSPDT |
Continuous |
— |
— |
— |
— |
— |
— |
0,8/3,0s |
— |
|
| RM7897A1002/U | 120Vac |
Primary |
HF/LF/Modulate |
Continuous |
Selectable |
• |
4/10s |
— |
0s |
— |
0,8/3,0s |
Uses S7800A1142/U display for programming, Valve proofing system: Integrated |
|
| RM7838B1013/U | 120Vac |
Full |
HF/LF/Modulate |
Continuous |
Interrupted |
• |
4/10s |
— |
— |
— |
0,8/3,0s |
— |
|
| EC7823A1004/U | 230Vac |
Full |
2xSPDT |
Continuous |
— |
— |
— |
— |
— |
— |
0,8/3,0s |
— |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| S7830A1005 | Expanded Annunciator to show additional information about faults in the limit string, only for use in Americas. Voltage: 120V, 50/60Hz. Uses Q7800 mounting base (not included). |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| R7849B1013/U | For UV sensors C7027/35/44. Ampli-Check. FFRT: EU=1.0s / US=0.8s |
|
| R7849B1021/U | For UV sensors C7027/35/44. Ampli-Check. FFRT: EU=2.0s / US=3.0s |
|
| R7851B1000/U | For UV sensors C7927 and visible light C7962. Ampli-Check. Not CE approved. FFRT: EU=2.0s / US=3.0s |
|
| R7851B1018/U | For UV sensors C7927 and visible light C7962. Ampli-Check. Not CE approved. FFRT: EU=1.0s / US=0.8s |
|
| R7824C1002/U | Used with RM7824A 24VDC model only. For UV sensor C7024E/F. Self-Check. Not CE approved. FFRT: 3.0s |
|
| R7851C1008/U | For UV sensors C7961E/F. Shutter-Check. Not CE approved. FFRT: EU=2.0s / US=3.0s |
|
| R7847A1025/U | For flame rod (cable<5m). FFRT: EU=1.0s / US=0.8s |
|
| R7852A1001/U | For IR sensors C7915. Not CE approved. FFRT: EU=2.0s / US=3.0s |
|
| R7847A1033/U | For flame rod (cable<5m). FFRT: EU=2.0s / US=3.0s |
|
| R7852B1009/U | For IR sensors C7915. Ampli-Check. Not CE approved. FFRT: EU=2.0s / US=3.0s |
|
| R7847A1074/U | For flame rod (cable>5m) and UV sensor C7012A/C/G. FFRT: EU=1.0s / US=0.8s |
|
| R7861A1026/U | For UV sensors C7061A/F. Shutter-Check. FFRT: EU=2.0s / US=3.0s |
|
| R7847A1082/U | For flame rod (cable>5m) and UV sensor C7012A/C/G. FFRT: EU=2.0s / US=3.0s |
|
| R7861A1034/U | For UV sensors C7061A/F. Shutter-Check. FFRT: EU=1.0s / US=0.8s |
|
| R7847B1023/U | For flame rod (cable<5m). Ampli-Check. FFRT: EU=1.0s / US=0.8s |
|
| R7886A1001/U | For UV sensors C7076A/D/F. Shutter-Check. FFRT: EU=2.0s / US=3.0s |
|
| R7847B1031/U | For flame rod (cable<5m). Ampli-Check. FFRT: EU=2.0s / US=3.0s |
|
| R7847B1064/U | For flame rod (cable>5m) and UV sensor C7012A/C/G. Ampli-Check. FFRT: EU=1.0s / US=0.8s |
|
| R7847B1072/U | For flame rod (cable>5m) and UV sensor C7012A/C/G. Ampli-Check. FFRT: EU=2.0s / US=3.0s |
|
| R7847C1005/U | For C7012E/F UV sensor. Shutter-Check. Not CE approved. FFRT: EU=2.0s / US=3.0s |
|
| R7849A1015/U | For UV sensors C7027/35/44. FFRT: EU=1.0s / US=0.8s |
|
| R7849A1023/U | For UV sensors C7027/35/44. FFRT: EU=2.0s / US=3.0s |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| S7800A1001/U | Language: English. With integrated Modbus communication option. |
|
| S7800A1035/U | Language: French |
|
| S7800A1043/U | Language: German |
|
| S7800A1050/U | Language: Italian |
|
| S7800A1068/U | Language: Spanish |
|
| S7800A1126/U | Language: Portuguese |
|
| S7800A1142/U | Language: English. Enhanced model, needed to program Enhanced 7800-series models (with VPS). |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| 203541/U | 5-wire connector for S7800/10/20 |
|
| 203765/U | Remote mounting bracket for S7800 |
|
| 205321B/U | Flush mounting bracket for S7800 |
|
| 221818A/U | Display extension cable assembly. Cable length 1.5 m |
|
| 50023821-002/U | Nema 4 cover assembly for remote mounting of S7800 display. Incl. remote reset button and wiring. |
|
| 50023821-001/U | Nema 4 cover assembly for remote mounting of S7800 display. |
|
| 221818C/U | Display extension cable assembly. Cable length ca. 3 m. Note: assure no electrical noise is present to avoid connection problems, due to extra long cable. |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| ST7800A1120/U | Prepurge time = 15.0min. |
|
| ST7800A1138/U | Prepurge time = 22.0min. |
|
| ST7800A1146/U | Prepurge time = 30.0min. |
|
| ST7800A1005/U | Prepurge time = 2s. |
|
| ST7800A1013/U | Prepurge time = 7s. |
|
| ST7800A1021/U | Prepurge time = 10s. |
|
| ST7800A1039/U | Prepurge time = 30s. |
|
| ST7800A1047/U | Prepurge time = 40s. |
|
| ST7800A1054/U | Prepurge time = 60s. |
|
| ST7800A1062/U | Prepurge time = 90s. |
|
| ST7800A1070/U | Prepurge time = 2.5min. |
|
| ST7800A1088/U | Prepurge time = 4.0min. |
|
| ST7800A1096/U | Prepurge time = 6.0min. |
|
| ST7800A1104/U | Prepurge time = 9.0min. |
|
| ST7800A1112/U | Prepurge time = 12.0min. |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| S7810A1009/U | Data Controlbus Module for communication or for remote S7800 mounting. |
|
| S7810M1003/U | MODBUS communication card. For US models only, not CE approved. |
|
| S7810M1029/U | MODBUS communication card. CE approved. |
|
| S7820A1007/U | Remote Reset Module. |
|
| Product Name | Description | Price (Excl. Tax) |
|---|---|---|
| Q7800A1005/U | Mounting subbase for 7800-series. Panel mount. |
|
| Q7800B1003/U | Mounting subbase for 7800-series. Wall mount. |
|
| Q7800F1004/U | Conversion subbase to replace RA890 devices by RM7890 or EC7890. |
|