UV flame sensors C7076A/D/F

UV flame sensor to detect ultraviolet radiation emitted by combustion flames.
Used with Honeywell burner controls to provide flame supervision in continuous operation for industrial burner applications, that use solid fuel or heavy oil, dirty gas, hydrogen, sulphur, etc. as fuel.
Approvals
CE approved according to EN298 only in combination with matching Honeywell flame amplifiers and burner controls.
Approved for use in continuous operation, by using dynamic self-check.
C7076F models are ATEX approved for use in explosion hazardous locations (zone 1)
C7076A/D models are UL/FM approved for use in the Americas
Additional description
Integrated air purge connection on standard model (C7076A).
Quick and easy installation on standard 1" NPT sight pipe.
applcertmarkcege23 applcertmarkfmnl05 applcertmarkulge51 applcertmarkexge51
Product Name ATEX Mechanical connection Ambient temperature (oC) Protection class Supply Voltage Note Price (Excl. Tax)
C7076A1007/U No 1" NPT -40 ... 70 IP65 110..120 Vac Shutter coil voltage: 120V only
C7076A1031/U No 1" NPT -40 ... 70 IP65 220..240 Vac
C7076F1006 Ex-proof enclosure (ATEX: II G Ex d IIC T6 Zone 1&2) 1 -40 ... 70 IP66 220..240 Vac Shutter coil voltage: 120V only
C7076F1014 Ex-proof enclosure (ATEX: II G Ex d IIC T6 Zone 1&2) 1 -40 ... 70 IP66 110..120 Vac Shutter coil voltage: 120V only
10327 €
Product Name Description Price (Excl. Tax)
118367A/U Swivel mount for adjustable positioning of the UV sensor
191053/U Ultraviolet sensing tube for C7076 sensor